Climate Control System Description - A/C Pressure Sensor
The A/C pressure sensor is attached to a receiver pipe of the A/C condenser exit side. This sensor uses the sensor that the output voltage changes by the pressure. The PCM receives the signal and is used to drive the A/C compressor. The PCM also controls the radiator fan and A/C condenser fan. When the A/C system pressure rises than an upper limit, or decreases than a lower limit, the PCM stops the A/C compressor to protect the system.

Upper Limit
2,850 kPa (29.07 kgf/cm2, 413.3 psi)
Lower Limit
196 kPa (2.00 kgf/cm2, 28.4 psi)
Fan Speed Change Point
A: 1,050 kPa (10.71 kgf/cm2, 152.3 psi)
B: 1,200 kPa (12.24 kgf/cm2 , 174.0 psi)
C: 1,350 kPa (13.77 kgf/cm2, 195.8 psi)
D: 1,500 kPa (15.30 kgf/cm2, 217.5 psi)

NOTE: This illustration is an example only. Appearance and structure of the actual parts may vary depending on the model.